When power on, thermostat displays “OFF”,all outputs are forced off. Touch S3 button to switch (manual/off/auto) mode, then press S2 to confirm and proceed power on/off setting. After power on, device displays current week, local time, working mode, current temperature, output status etc.
In normal working status, press S4 or S5 button will enter into temperature setting interface.
The setting range is 5-37 ℃(41-99℉). Then press S4 or S5 can adjust the value. Press S3 or wait 25 seconds without any key operation will save the setting and return back to the normal operation interface.
Vacation Mode: The changed value will be valid until next setting.
Key lock function
In normal operating interface, long press S1+S4 button, icon appear that indicates the button is locked, at this time all buttons are disabled; When long press S1+S4 button again, icon disappear that indicates the button is unlocked, all buttons back to normal work.
Control specifications
- Detection temperature < setting temperature - 0.5℃, output turns on, and output icon displays.
- Detection temperature ≥ setting temperature + 0.5℃, output turns off, and output icon disappears.
Manual / Auto mode setting
In normal display interface, touch S3 button can switch between Manual and Auto mode.
Choose the mode you may need and press S2 button to save the setting.
Auto Mode: Device will follow the preset time periods and temperature to control heating system automatically.
Manual Mode: Device will follow the manual setting temperature to control the heating system.
Vacation mode setting
- In normal working interface, if vocation mode is not activated, long press S2 button to enter vacation mode temperature setting. The default temperature is 10 ℃, and setting range is 5-37 ℃(41-98℉). Press S4 or S5 to adjust the value, then press S3 or wait 25 seconds to save the setting and return to the normal working interface. In this time vacation mode icon displays, and device will follow the setting.
- Long press S2 again will end vacation mode and resume to normal work, vacation mode icon
will be disappeared.
Local Time Setting
- In normal working interface, long press S1 to enter into local time setting interface.
- In local time setting interface, press S4 or S5 button to set the “week, hour & minute” parameter, and press S1 button can switch among the “week, hour & minute”.
- After finish the local time setting, press S1 or wait 25 seconds without any key operation will save the setting and return to normal display.
Auto Mode Time Periods Parameter Setting
- In normal working interface, short press S1 to enter into time periods setting. Four time periods can be set for each day of the whole week.
- Press S2 can switch among “Hours, Minutes, Temperature value”. Press S4 or S5 can change the value.
- After finished the setting of 4 time periods on Monday, press S1 and follow the same way to set periods of next days.
- After all periods set, press S1 /S2 or wait 25 seconds without any key operation will save the setting and return to normal display. Device will operate in accordance with the new setting.
The default setting is as follow:
High temperature protection
When external temperature sensor detect the temperature value≥55℃, device will open high temperature protection, electric heating will be forced off, and high temperature protection icon displays.
When external temperature sensor detect the temperature value<50 ℃, device will return to normal work, high temperature protection icon disappears.
Anti-freeze protection function: (Optional)
In shutdown interface:
- When the built-in temperature sensor detect the temperature value≤5℃, device will open anti-freeze protection, electric heating will be forced open, and anti-freeze protection icon displays.
- When the built-in temperature sensor detect the temperature value>8 ℃, device will turn off anti-freeze protection and return to normal work, anti-freeze icon disappears.
Note: If MH7 thermostat do not connect with an external temperature sensor, it will only display the indoor temperature icon; If MH7 thermostat connect with an external temperature sensor, it will display the indoor temperature and high temperature protection icon; When it is under high temperature protection, high temperature protection icon flickers.
Humidity display operation
In normal working interface, long press S1+S5 buttons and enter into humidity display interface, when press S1+S5 buttons again, it will back to the normal interface.
In shutdown state, long press S3+S5 synchronically can enter into secret menu. Press S4 or S5 to enter code 1234. Touch S3 to enter setting interface. Following are parameters which can be set.

* After power failure:
0 indicates device will be in shutdown state (“OFF”) when power on again;
1 indicates device will be in working interface when power on again;
2 (default) indicates device will stay the status before power failure when power on again.