Quickstart

This is a secure On/Off Power Switch for XXXQFrequencyName. To run this device please connect it to your mains power supply.



Important safety information

Please read this manual carefully. Failure to follow the recommendations in this manual may be dangerous or may violate the law. The manufacturer, importer, distributor and seller shall not be liable for any loss or damage resulting from failure to comply with the instructions in this manual or any other material. Use this equipment only for its intended purpose. Follow the disposal instructions. Do not dispose of electronic equipment or batteries in a fire or near open heat sources.

Product Description

FIBARO Wall Plug is a remotely controlled plug-in switch with the ability to measure power and energy consumption. It uses a LED frame to visualize the current load and operating mode with color changing illumination. FIBARO Wall Plug makes it possible to control electrical devices in a convenient and maintenance-free way.It is also equipped with a USB charging port with power metering.Main features of FIBARO Wall Plug:- Compatible with type G sockets and plugs.- Compatible with any Z-Wave or Z-Wave+ Controller.- Supports Z-Wave network Security Modes: S0 with AES-128 encryption and S2 with PRNG-based encryption.- Extremely easy installation - simply plug the device into the mains socket.- Equipped with USB charging port.- Works as a Z-Wave signal repeater.- Active power and energy consumption metering for plugged device and the USB port.- Current value of the load and operating mode are indicated by the multi-color LED frame.

Reset to factory default XXXResetDescription
Inclusion XXXInclusionDescription
Exclusion XXXExclusionDescription
NIF XXXNIF
Wakeup XXXWakeupDescription
Protection XXXProtection
FirmwareUpdate XXXFirmwareUpdate
SetAssociation XXXSetAssociation

Association Groups:

Group Number Maximum Nodes Description
1 1 Lifeline reports the device status and allows for assigning single device only (main controller by default).
2 5 On/Off (Button) devices in this group will be switched on or off when relay status is changed using the button (uses Basic command class).
3 5 On/Off (Plug power) devices in this group will be switched on or off depending on the current load of plugged device (uses Basic command class).

Configuration Parameters

Parameter 11: Power reporting

This parameter determines the minimum percentage change in active power consumption (in relation to the previously reported) that will result in sending new power report.
Size: 1 Byte, Default Value: 15

Setting Description
0 power reports inactive
1 - 100 power change in percent

Parameter 12: Energy reporting threshold

This parameter determines the minimum change in energy consumption (in relation to the previously reported) that will result in sending a new report.
Size: 2 Byte, Default Value: 10

Setting Description
0 energy reports inactive
1 - 500 (0.01-5kWh, step 0.01kWh) - threshold

Parameter 13: Periodic power reporting

This parameter defines time period between independent reports sent when changes in power load have not been recorded or if changes are insignificant. By default reports are sent every hour.
Size: 2 Byte, Default Value: 3600

Setting Description
0 periodic reports inactive
30 - 32400 (in seconds)

Parameter 14: Periodic energy reporting

This parameter defines time period between independent reports sent when changes in power load have not been recorded or if changes are insignificant. By default reports are sent every hour.
Size: 2 Byte, Default Value: 3600

Setting Description
0 periodic reports inactive
30 - 32400 (in seconds)

Parameter 15: Measuring energy consumed by the Wall Plug itself

This parameter determines whether power metering should include the amount of power consumed by the Wall Plug itself. Results are being added to the value of power consumed by controlled device.
Size: 1 Byte, Default Value: 0

Setting Description
0 function inactive
1 function active

Parameter 2: Remember device status before the power failure

This parameter determines how the Wall Plug will react in the event of power supply failure (e.g. power outage or taking out from the electrical outlet). After the power supply is back on, the Wall Plug can be restored to previous state or remain switched off.
Size: 1 Byte, Default Value: 1

Setting Description
0 device remains switched off
1 device restores the state from before the power failure

Parameter 21: UP value - On/Off (Power) association group (3)

Upper power threshold, used in parameter 23. UP value cannot be lower than a value specified in parameter 22.
Size: 2 Byte, Default Value: 500

Setting Description
100 - 30000 (10.0-3000.0W, step 0.1W)

Parameter 22: DOWN value - On/Off (Power) association group (3)

Lower power threshold, used in parameter 23. DOWN value cannot be higher than a value specified in parameter 21.
Size: 2 Byte, Default Value: 300

Setting Description
0 - 29900 (0.0-2990.0W, step 0.1W)

Parameter 23: Controlling On/Off (Power) association group (3)

This parameter defines the way that 3rd association group devices are controlled. Depends on the actual measured power (according to parameters 21 and 22 settings).
Size: 1 Byte, Default Value: 3

Setting Description
1 send frame (with value set in parameter 26) only if power exceeded value of parameter 21
2 send frame (with value set in parameter 27) only if power dropped below value of parameter 22
3 send frame in both cases

Parameter 24: SWITCH ON value - On/Off (Button) association group (2)

The value of BASIC SET command frame sent to the devices associated in 2nd group On/Off (Button) when turning the device ON using the button.
Size: 2 Byte, Default Value: 255

Setting Description
0 turning off associated devices
1 - 99 forcing level of associated devices
255 setting associated devices to the last remembered state or turning them on

Parameter 25: SWITCH OFF value - On/Off (Button) association group (2)

The value of BASIC SET command frame sent to the devices associated in 2nd group On/Off (Button) when turning the device OFF using the button.
Size: 2 Byte, Default Value: 0

Setting Description
0 turning off associated devices
1 - 99 forcing level of associated devices
255 setting associated devices to the last remembered state or turning them on

Parameter 26: THRESHOLD UP value - On/Off (Power) association group (3)

The value of BASIC SET command frame sent to the devices associated in 3rd group On/Off (Power) if power exceeded value of parameter 21.
Size: 2 Byte, Default Value: 255

Setting Description
0 turning off associated devices
1 - 99 forcing level of associated devices
255 setting associated devices to the last remembered state or turning them on

Parameter 27: THRESHOLD DOWN value - On/Off (Power) association group (3)

The value of BASIC SET command frame sent to the devices associated in 3rd group On/Off (Power) if power dropped below value of parameter 22.
Size: 2 Byte, Default Value: 0

Setting Description
0 turning off associated devices
1 - 99 forcing level of associated devices
255 setting associated devices to the last remembered state or turning them on

Parameter 3: Overload safety switch

This function allows to turn off the controlled device in case of exceeding the defined power.Controlled device can be turned back on via button or sending a control frame. By default this function is inactive.
Size: 2 Byte, Default Value: 0

Setting Description
0 function inactive
10 - 30000 1.0-3000.0W, step 0.1W) - power threshold

Parameter 30: Active alarms

Define Z-Wave network alarms to which the Wall Plug will respond.
Size: 1 Byte, Default Value: 63

Setting Description
1 general alarm
2 smoke alarm
4 CO alarm
8 CO2 alarm
16 high temperature alarm
32 flood alarm

Parameter 31: Response to alarm frames

This parameter defines how the Wall Plug will respond to alarms (devicesstatus change).In case of values 1 or 2 the Wall Plug is operating normally and LED frame signals an alarm through time defined in parameter 32 or until the alarm is canceled.In case of values 5 to 50 the Wall Plug does not report status change, power changes, ignores BASIC SET command frames. After time defined in parameter 32 or after the alarm cancellation, connected device is set to the previous state.
Size: 1 Byte, Default Value: 0

Setting Description
0 no reaction
1 turn connected device on
2 turn connected device off
5 - 50 (0.5-5.0s, step 0.1s) - cyclically change device state with set period

Parameter 32: Alarm state duration

This parameter specifies the duration of alarm state. If a device sending an alarm frame through the Z-Wave network sets alarm duration as well, this settings are ignored.
Size: 2 Byte, Default Value: 600

Setting Description
1 - 32400 (in seconds)

Parameter 40: Power load for violet color

This parameter determines maximum active power value, which when exceeded, causes the LED frame to flash violet. Function is active only when parameter 41 is set to 1 or 2.
Size: 2 Byte, Default Value: 30000

Setting Description
1000 - 30000 (100.0-3000.0W, step 0.1W)

Parameter 41: LED frame color when controlled device is on

When set to 1 or 2, LED frame color will change depending on active power and parameter 40. Other colors are set permanently and do not depend on powerconsumption.
Size: 1 Byte, Default Value: 1

Setting Description
0 illumination turned off completely
1 color changes smoothly depending on active power
2 color changes in steps depending on active power
3 white
4 red
5 green
6 blue
7 yellow
8 cyan
9 magenta

Parameter 42: LED frame color when controlled device is off

This parameter defines the illumination color after turning off.
Size: 1 Byte, Default Value: 0

Setting Description
0 illumination turned off completely
1 LED frame is illuminated with a color corresponding to the last measured power, before the controlled device was turned off
3 white
4 red
5 green
6 blue
7 yellow
8 cyan
9 magenta

Parameter 43: LED frame color at the Z-Wave network alarm detection

This parameter defines the illumination color in case of Z-Wave alarm.
Size: 1 Byte, Default Value: 2

Setting Description
0 illumination turned off completely
1 no change in color. LED frame color is determined by settings of parameters 41 or 42
2 LED frame flashes red/blue/white
3 white
4 red
5 green
6 blue
7 yellow
8 cyan
9 magenta

Technical Data

Hardware Platform ZM5101
Device Type On/Off Power Switch
Network Operation Always On Slave
Firmware Version HW: 1 FW: 4.02:04.02
Z-Wave Version 6.71.01
Certification ID ZC10-19086711
Z-Wave Product Id 0x010F.0x1501.0x1000
Firmware Updatable Updatable by Consumer by RF
Loads Controlled 3
Sensors Power
Supported Meter Type Electric Energy
Supported Notification Types Power ManagementSystem
Color White
Electric Load Type IncandescentInductive (e.g. Motor)
Frequency XXfrequency
Maximum transmission power XXantenna
CEPT (Europe)On/Off Power Switch