Quickstart

This is a Alarm Sensor for Europe. To run this device please connect it to your mains power supply. To put the device into inclusion mode, turn the device‘s control dial (E) to "Set" and back to "0" within 5 seconds.



Important safety information

Please read this manual carefully. Failure to follow the recommendations in this manual may be dangerous or may violate the law. The manufacturer, importer, distributor and seller shall not be liable for any loss or damage resulting from failure to comply with the instructions in this manual or any other material. Use this equipment only for its intended purpose. Follow the disposal instructions. Do not dispose of electronic equipment or batteries in a fire or near open heat sources.

What is Z-Wave?

Z-Wave is the international wireless protocol for communication in the Smart Home. This device is suited for use in the region mentioned in the Quickstart section.

Z-Wave ensures a reliable communication by reconfirming every message (two-way communication) and every mains powered node can act as a repeater for other nodes (meshed network) in case the receiver is not in direct wireless range of the transmitter.

This device and every other certified Z-Wave device can be used together with any other certified Z-Wave device regardless of brand and origin as long as both are suited for the same frequency range.

If a device supports secure communication it will communicate with other devices secure as long as this device provides the same or a higher level of security. Otherwise it will automatically turn into a lower level of security to maintain backward compatibility.

For more information about Z-Wave technology, devices, white papers etc. please refer to www.z-wave.info.

Product Description

Are you toying with the idea of fitting a motion detector to your building? The infrared controlled IS 140-2 motion detector gives you all the benefits of a modern detector. Needless to say, we always use the very latest technology for our bestsellers too. For instance, we have given the product in its current generation even more class: larger adjustment angle, even longer reach and even better detection performance. Treat your home to intelligent sensor technology.

Prepare for Installation / Reset

Please read the user manual before installing the product.

In order to include (add) a Z-Wave device to a network it must be in factory default state. Please make sure to reset the device into factory default. You can do this by performing an Exclusion operation as described below in the manual. Every Z-Wave controller is able to perform this operation however it is recommended to use the primary controller of the previous network to make sure the very device is excluded properly from this network.

Reset to factory default

This device also allows to be reset without any involvement of a Z-Wave controller. This procedure should only be used when the primary controller is inoperable.

1) Turn the device‘s control dial (E) to "Set" and move it to "Reset" within 5 seconds.
2) The status LED (F) briefly flashes to show that the light has been reset.
3) The device is now no longer included in the Z-Wave system and has been returned to factory settings.

Safety Warning for Mains Powered Devices

ATTENTION: only authorized technicians under consideration of the country-specific installation guidelines/norms may do works with mains power. Prior to the assembly of the product, the voltage network has to be switched off and ensured against re-switching.

Installation

Electrical installation

• Switch OFF power supply (Fig. 3.5)

Connecting the mains supply lead The mains leads consists of at least a 3-core cable:
L = Phase conductor (usually black or brown)
N = Neutral conductor (usually blue)
PE = Protective-earth conductor (usually green/yellow)

If you are in any doubt, identify the conductors using a voltage tester; then disconnect from the power supply again. Loop through any protective-earth conductor.

Important: incorrectly wired connections will produce a short circuit later on in the product or your fuse box. In this case, you must identify the individual leads and reconnect them. An appropriate power switch for switching ON and OFF can be installed in the supply lead. The electric circuit must be protected by a 10 A circuit breaker. Connection diagram (Fig. 3.5)



Mounting

• Check all components for damage.
• Do not use the product if it is damaged.
• Select an appropriate mounting location, taking the reach and motion detection into consideration (Fig. 4.1). The most reliable way of detecting movement is to install the sensor aimed across the direction in which a person would walk and by ensuring that
no obstacles (such as trees, walls etc.) obstruct the line of sensor vision. (Fig. 4.2 / 4.3) Mounting procedure 
• Switch OFF power supply.
• Detach enclosure from wall mount . (Fig. 4.5)
• Mark drill holes. (Fig. 4.6)
• Drill holes and fit wall plugs. (Fig. 4.7)
• Fit sealing plug. (Fig. 4.8) 
– Concealed power supply lead (Fig. 4.9)
– Concealed power supply lead with spacers (Fig. 4.10)
• Drill condensation water drainage hole with a 5 mm drill bit. (Fig. 4.11)
• Connect conductors. (Fig. 4.12 / 4.13)
• Fit enclosure onto wall mount. (Fig. 4.14)
• Screw in retaining screws. (Fig. 4.15)
• Switch ON power supply. (Fig. 4.15)





Inclusion/Exclusion

On factory default the device does not belong to any Z-Wave network. The device needs to be added to an existing wireless network to communicate with the devices of this network. This process is called Inclusion.

Devices can also be removed from a network. This process is called Exclusion. Both processes are initiated by the primary controller of the Z-Wave network. This controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is then performed doing a special manual action right on the device.

Inclusion

To put the device into inclusion mode, turn the device‘s control dial (E) to "Set" and back to "0" within 5 seconds.

Exclusion

Exclusion = Remove To start the motion detector‘s exclusion mode, turn the device‘s control dial (E) to "Set" and back to "0" within 5 seconds.

Product Usage

The motion detector will also work without being integrated into a Z-Wave network. In this case, the  time setting is permanently set to 3 minutes. When putting the motion detector into operation, it will switch OFF after the 10-second calibration phase and is then activated for sensor mode. The motion detector can now be integrated into the Z-Wave network. The settings can be made via the control dials or via Z-Wave network. The settings last selected will always be in effect regardless of whether they were made via the control dials or via Z-Wave network.

Factory settings
Twilight level (C): 2000 lux
Time setting: 3 min

Twilight setting (Fig. 5.1/C)
can be infinitely varied
Control dial set to moon = twilight operation, approx. 2 lux
Control dial set to sun = daylight operation, approx. 2000 lux
Note: To adjust the detection zone in daylight, the control dial must be set to sun = daylight operation.

Reach setting/adjustment
The detection zone can be optimised to suit requirements.
Sensor unit
–– Sensor unit swivels through 180°. (Fig. 5.2)
–– Sensor unit tilts through 90°. (Fig. 5.5)

Adhesive shrouds (Fig. 5.3) The film shroud can be used for masking out any number of lens segments to limit reach as required. Inadvertent triggering is ruled out or the sensor can be targeted to watch over danger spots. (Fig. 5.4)




Quick trouble shooting

Here are a few hints for network installation if things dont work as expected.

  1. Make sure a device is in factory reset state before including. In doubt exclude before include.
  2. If inclusion still fails, check if both devices use the same frequency.
  3. Remove all dead devices from associations. Otherwise you will see severe delays.
  4. Never use sleeping battery devices without a central controller.
  5. Dont poll FLIRS devices.
  6. Make sure to have enough mains powered device to benefit from the meshing

Association - one device controls an other device

Z-Wave devices control other Z-Wave devices. The relationship between one device controlling another device is called association. In order to control a different device, the controlling device needs to maintain a list of devices that will receive controlling commands. These lists are called association groups and they are always related to certain events (e.g. button pressed, sensor triggers, ...). In case the event happens all devices stored in the respective association group will receive the same wireless command wireless command, typically a 'Basic Set' Command.

Association Groups:

Group Number Maximum Nodes Description
1 1 Lifeline
2 5 Relay Switch
3 5 Motin begin/end - Relay Switch
4 16 Ambient light- Multilevel Sensor Report

Configuration Parameters

Z-Wave products are supposed to work out of the box after inclusion, however certain configuration can adapt the function better to user needs or unlock further enhanced features.

IMPORTANT: Controllers may only allow configuring signed values. In order to set values in the range 128 ... 255 the value sent in the application shall be the desired value minus 256. For example: To set a parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56. In case of a two byte value the same logic applies: Values greater than 32768 may needed to be given as negative values too.

Parameter 1: TIME

Duration of light after motion detection.
Size: 2 Byte, Default Value: 180

Setting Description
5 - 900 seconds

Parameter 2: LIGHT

Light threshold [ lx ]Value can be controlled via potentiometer - potentiometer value isused as the default value and any potentiometer movement rewritesthe current setting.
Size: 2 Byte, Default Value: 2000

Setting Description
0 run Learn ambient light sequence (the level is set automatically)
2 - 1999 lux
2000 2000 - is used as daylight ( always night mode)

Parameter 5: SENSITIVITY

Motion Sensor (PIR) Sensitivity [%]Value can be controlled via potentiometer - potentiometer value isused as the default value and any potentiometer movement rewritesthe current setting
Size: 1 Byte, Default Value: 100

Setting Description
2 - 100 %

Parameter 8: GLOBAL_LIGHT

Use External Ambient Light ValueWhen GLOBAL_LIGHT mode is ON - device overrides its own lightsensor values and uses Light report values from any Z-Wave lightsensor instead - this has to be configured appropriately to send lightautomatically.If the last remote light level value is older than 30 minutes, the internallight value is used again until the next external value is received.
Size: 1 Byte, Default Value: 1

Setting Description
0 OFF function
1 ON function

Parameter 9: SLAVE_MODE

Can disable sensor controllu201cStupidu201d mode (bit 2 = 1): - has higher priority then slave mode. - lamp is permanently on (usefull for simple power wall switch controlling).Slave mode ( bit 0 = 1 ):- only if included in Z-Wave network- usefull for controlling via third-party sensor- relay is directly controlled via Z-Wave, internal sensors are not used for controlling it.Central unit checking ( bit 1 = 1 ):( usefull especialy for controlling via gateway ) When Slave bit is 0:- lamp signalises fail of lifeline connection ( if this bit is zero fail of lifeline connection is not signalised ) When slave bit is 1:- device checks presence of Z-Wave device in lifeline group ( gateway ). If it is not present for 2 minutes ( testing repeatedly every 30 seconds ) device switches to normal mode in the same way as after the end of local disabled mode ( ON_BEHAVIOUR )- The device checks every 1 minute for recovery of Lifeline connection.- if no lifeline specified - it works in normal modeBe careful with this option, lamp stops using itu2019s own motion sensor in Slave and Stupid mode.
Size: 1 Byte, Default Value: 2

Setting Description
0 Normal mode
1 Slave mode without gateway checking
2 Normal mode with lifeline error signalisation
3 Slave mode with gateway checking
4 Stupid mode - lamp permanetly on

Parameter 10: OFF_BEHAVIOUR

Behaviour after BASIC OFF ( and similar commands ).If a transition ( even with zero change ) with a non-default duration isto be processed, the transition cannot be interrupted by any motionevent in any case.for values 1-209 - Lamp is switched off and remains so until after a specified timeout once a new motion event (local or remote) is received.
Size: 2 Byte, Default Value: 10

Setting Description
0 Lamp is switched off and remains so until any new motion event (local or remote) is received.
1 - 100 timeout: 1 second (1) to 100 seconds (100) in 1-second resolution
101 - 200 timeout: 1 minute (101) to 100 minutes (200) 1-minute resolution
201 - 209 timeout: 1 hour (201) to 9 hours (209) in 1-hour resolution
255 Lamp is switched off for TIME (cfg 1). It does not wait for a motion event and works normally via current motion evaluation

Parameter 11: ON_BEHAVIOUR

Behaviour after BASIC ON (and similar commands).If a transition (even with zero change) with a non-default duration is to be processed, the transition cannot be interrupted by any motion event in any case.for values 1-209 - Lamp is switched on and remains so until after a specified timeout once a new motion event (local or remote) is received. It then works normally via current motion evaluation.
Size: 2 Byte, Default Value: 255

Setting Description
0 Lamp is switched on and remains so until any new motion event (local or remote) is received. It then works normally via current motion evaluation. Notice - during the day, this mode cannot be ended remotely due to motion events not being transmitted - only via local motion sensor if enabled.
1 - 100 timeout: 1 second (1) to 100 seconds (100) in 1-second resolution
101 - 200 timeout: 1 minute (101) to 100 minutes (200) 1-minute resolution
201 - 209 timeout: 1 hour (201) to 9 hours (209) in 1-hour resolution
255 Lamp is switched on for TIME (cfg 1). It does not wait for a motion event and works normally via current motion evaluation.

Parameter 12: ON_TIME_OVER

Time limit to stop waiting for motion after timeout of ON_BEHAVIOURor OFF_ON_BEHAVIOUR ( 0-209 ) to prevent staying ON forever whenis no motion.
Size: 2 Byte, Default Value: 204

Setting Description
0 o additional waiting for motion.
1 - 100 timeout: 1 second (1) to 100 seconds (100) in 1-second resolution
101 - 200 timeout: 1 minute (101) to 100 minutes (200) 1-minute resolution
201 - 209 timeout: 1 hour (201) to 9 hours (209) in 1-hour resolution
255 Never stop waiting before motion.

Parameter 13: ON_OFF_BEHAVIOR

Behaviour after after a rapid sequence of BASIC ON and BASIC OFF commands.The intention is to use a much longer timeout value than the time after a single ON command which should then be followed by a short timeout value.The behaviour is almost the same as for parameter 10 (OFF_LOCAL_DISABLE) for values 1-209 - Lamp is switched off and remains so until after a specified timeout once a new motion event (local or remote) is received.
Size: 2 Byte, Default Value: 204

Setting Description
0 Lamp is switched off and remains so until any new motion event (local or remote) is received.
1 - 100 timeout: 1 second (1) to 100 seconds (100) in 1-second resolution
101 - 200 timeout: 1 minute (101) to 100 minutes (200) 1-minute resolution
201 - 209 timeout: 1 hour (201) to 9 hours (209) in 1-hour resolution
255 device ignores ON - OFF sequence and uses OFF behavior

Parameter 14: OFF_ON_BEHAVIOUR

Behaviour after after a rapid sequence of BASIC OFF and BASIC ONcommands.The intention is to use a much longer timeout value than the time aftera single OFF command which should then be followed by a shorttimeout value.The behaviour is amost the same as for parameter 11for values 1-209 - Lamp is switched on and remains so until after a specified timeout once a new motion event (local or remote) is received. It then works normally via current motion evaluation.
Size: 2 Byte, Default Value: 204

Setting Description
0 Lamp is switched on and remains so until any new motion event (local or remote) is received. It then works normally via current motion evaluation. Notice - during the day, this mode cannot be ended remotely due to motion events not being transmitted - only via local motion sensor if enabled.
1 - 100 timeout: 1 second (1) to 100 seconds (100) in 1-second resolution.
101 - 200 timeout: 1 minute (101) to 100 minutes (200) 1-minute resolution
201 - 209 timeout: 1 hour (201) to 9 hours (209) in 1-hour resolution
255 device ignores OFF - ON sequence and uses ON behaviour

Parameter 15: SEQUENCY_TIME

Time in [ 100 miliseconds ] of maximum delay between BASIC ONand BASIC OFF ( and vice versa ) to consider this as a sequence. It istypically 1 second, but can be exceptionally longer due to retransmissionsand overload - in this case, a longer interval can be allowed ( upto 5 seconds ).
Size: 1 Byte, Default Value: 255

Setting Description
10 - 50 tenth of second

Parameter 16: MOTION_DISABLE

Motion disable timeout after BASIC SET to motion endpoint when theinternal motion sensor is not used for evaluating the behaviour of thelamp and groups 2 and 3. Events are, however, still transmitted to theLifeline, and the lamp can be controlled via remote motion sensors.for values 1-209 - Internal motion sensor is disabled for specified timeout after BASIC SET 0x00 to Motion endpoint.
Size: 2 Byte, Default Value: 0

Setting Description
0 BASIC SET to Motion sensor endpoint ignored, BASIC to root is mapped to relay endpoint, motion sensor still enabled
1 - 100 timeout: 1 second (1) to 100 seconds (100) in 1-second resolution
101 - 200 timeout: 1 minute (101) to 100 minutes (200) 1-minute resolution
201 - 209 timeout: 1 hour (201) to 9 hours (209) in 1-hour resolution
255 BASIC SET to Motion sensor endpoint ignored, BASIC to root is mapped to relay endpoint, motion sensor still disabled

Technical Data

Dimensions 86 x 70 x 95 mm
Weight 170 gr
Hardware Platform ZM5202
EAN 4007841029807
IP Class IP 54
Voltage 230 V
Load 100 W
Device Type Notification Sensor
Network Operation Always On Slave
Firmware Version 00.26
Z-Wave Version 04.26
Certification ID ZC10-17045540
Z-Wave Product Id 0x0271.0x0002.0x1a72
Supported Notification Types Home SecuritySystem
IP (Ingress Protection) Rated ok
Firmware Updatable Updatable by Consumer by RF
Neutral Wire Required ok
Sensors LuminanceMotion/No Motion (Binary)
Outdoor Use ok
Electric Load Type
Frequency Europe - 868,4 Mhz
Maximum transmission power 5 mW

Supported Command Classes

  • Basic
  • Switch Binary
  • Switch All
  • Sensor Multilevel
  • Association Grp Info
  • Device Reset Locally
  • Zwaveplus Info
  • Multi Channel
  • Configuration
  • Alarm
  • Manufacturer Specific
  • Powerlevel
  • Node Naming
  • Firmware Update Md
  • Association
  • Version
  • Multi Channel Association
  • Sensor Configuration

Controlled Command Classes

  • Basic

Explanation of Z-Wave specific terms

  • Controller — is a Z-Wave device with capabilities to manage the network. Controllers are typically Gateways,Remote Controls or battery operated wall controllers.
  • Slave — is a Z-Wave device without capabilities to manage the network. Slaves can be sensors, actuators and even remote controls.
  • Primary Controller — is the central organizer of the network. It must be a controller. There can be only one primary controller in a Z-Wave network.
  • Inclusion — is the process of adding new Z-Wave devices into a network.
  • Exclusion — is the process of removing Z-Wave devices from the network.
  • Association — is a control relationship between a controlling device and a controlled device.
  • Wakeup Notification — is a special wireless message issued by a Z-Wave device to announces that is able to communicate.
  • Node Information Frame — is a special wireless message issued by a Z-Wave device to announce its capabilities and functions.